Design of Air-Cooled Microchannel Condensers for Mal-Distributed Air Flow Conditions


STSL Home

Up Laboratory Dr. Garimella Publications Students


Mechanical Engineering Home

Background

Microchannel-tube, multilouver-fin heat exchangers are fast replacing conventional round-tube, plate-fin condensers, particularly in automotive air-conditioning applications. The larger air-side heat transfer coefficients due to the louvers and the larger surface area per unit volume of these heat exchangers are believed to lead to more compact geometries. The basic geometry of a microchannel condenser is shown in Figure 1.

Motivation

This work was driven by the need to improve the efficiency of residential air-conditioning condensers. An improvement in efficiency can lead to more compact geometry, resulting in savings in material cost. Compact geometries can also result in the reduction of required refrigerant charge. Besides savings in cost, reduction in refrigerant charge also leads to environmental benefits in the form of reduced ozone depletion and global warming. Keeping these environmental benefits in mind, refrigerant R-410A, which has zero ozone depletion and global warming potential, was used for this study.

Past Work / Need For Research

Figure 2 Cause of air flow mal-distribution

A typical condenser unit of an air conditioning system is shown in Figure 2. The condenser coils are vertically placed along the four sidewalls of the condenser unit. Air flow over the condenser coils is generated by an induced draft fan placed at the top of the unit. This configuration results in a non-uniform air flow through the condenser coils. Hence a uniform air flow distribution, which is assumed in most theoretical studies, is an idealization. A study of the condenser performance for mal-distributed air flow conditions is required.

Specific Objectives

· Optimize microchannel condenser geometry for minimum material and energy costs

· Analyze the performance of microchannel condenser under realistic, mal-distributed air flow conditions

· Modify the condenser geometry for optimal performance under these mal-distributed air flow conditions

Approach

The condenser performance was numerically analyzed by dividing the condenser into small segments along the length. The heat transfer calculations in each segment were performed using the Effectiveness-NTU method. The refrigerant properties for each segment were calculated based on the conditions and the center of that segment. As the conditions at the center of a segment were not initially known, the calculations were done iteratively with a stop criterion of less than 0.1% variation in the calculated heat duty in successive iterations.

Sample Findings

 

 

 

 

 

 

 

 

 

 

 

Figure 3 Heat transfer coefficient and heat duty distribution

 

Above figure shows a plot of the air-side, tube-side and overall heat transfer coefficients and segment heat duty.

Figure 4 Optimization for Uniform Air Flow

For a uniform air flow, various condenser geometric parameters were optimized to provide the design heat duty of 14.5 kW with minimum condenser mass. The variation of condenser mass, height and length along this optimization procedure is shown in above.

Figure 5 Effect of air flow mal-distribution

The inlet air flow to the condenser was then mal-distributed linearly up to a 50% mal-distribution. The effect of such a mal-distribution is shown in figure 5. There was found to be a maximum increase of 7% in the required condenser mass due to these mal-distributions.

Figure 6 Optimum design for mal-distributed air flow

The condenser’s fin geometry was then modified to specifically compensate for this drop in performance due to air flow mal-distribution. The fin density in the condenser was distributed so as to have a higher fin density distribution at regions of the condenser where the air flow was low and have a lower fin density at regions of high air flow rate. This design improvement reduced the required condenser mass by up to 3%. This is shown in figure 6.
Important Implications

The present work highlights the need for condenser design to include the effect of mal-distributed air flow conditions. It was shown that air flow mal-distribution significantly alters condenser performance, so as to justify the use of modified fin distributions to counter this air flow mal-distribution.

Applications

The design procedure presented in the current work can be used as a tool for efficient microchannel condenser design. A set of design constraints were used in the current work. These constraints could be modified to suit the specific application. Also the ease of manufacture and first cost of the optimum geometry needs to be considered, while designing for a real-life application.

Ongoing Work / Future Directions
Air flow mal-distributions from the top to bottom of the condenser were considered in the present study. In the future, potential lateral mal-distributions and non linear vertical distributions of air flow should be investigated. Also the modifications made in the air-side geometry to improve condenser performance might affect the upstream inlet air flow pattern available to the condenser. The condenser design for mal-distributed air flow could be further improved to account for this cross effect of change in inlet air flow pattern due to modifications in downstream air-side geometry. Furthermore, in all case investigated here, the air inlet temperature was assumed to be uniform across the condenser. Mal-distributed temperatures should be investigated in further studies. Refrigerant flow across different tubes within a pass was also assumed to be uniform in this study; however in actual condensers, refrigerant flow non-uniformities exist due to poor header design and fabrication. An investigation of the effect of refrigerant mal-distribution on condenser performance would complement this study. Finally, the results from this study should be validated experimentally, and the effect of condenser design optimization on the system-level performance of an air-conditioning system should be investigated. As part of this, the capital costs involved in implementing the design geometries with non-uniform air-side geometries should be studied.
Papers
  1. Subramaniam, Vishwanath and Garimella, Srinivas, “Design of air-cooled R-410A microchannel condensersASHRAE Transactions, v 111 part 1, p 471-486

DISCLAIMER